“Siemens 216 2AD23 0XB0 CPU 226 dc dc dc” has been added to your cart. View cart

Siemens 6ES7 315 2EH14 0AB0 CPU 315 2 PN DP
Description
Siemens 6ES7 315 2EH14 0AB0 CPU 315 2 PN DP is the SIMATIC S7-300 Central processing unit with 384 KB work memory, This PLC Siemens 6ES7 315 2EH14 0AB0 CPU 315 2 PN DP Has many features and powerful function,1st interface MPI/DP 12 Mbit/s, 2nd interface Ethernet PROFINET, with 2-port switch, Micro Memory Card required
Specification of Siemens 6ES7 315 2EH14 0AB0 CPU 315 2 PN DP
Part number | 6ES7315-2EH14-0AB0 |
General information | |
HW functional status | 1 |
Firmware version | V3.2 |
Product function | |
● Isochronous mode | Yes; Via PROFIBUS DP or PROFINET interface |
Engineering with | |
● Programming package | STEP 7 V5.5 or higher |
Supply voltage | |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
external protection for power supply lines (recommendation) | 2 A min. |
Mains buffering | |
● Mains/voltage failure stored energy time | 5 ms |
● Repeat rate, min. | 1 s |
Input current | |
Current consumption (rated value) | 750 mA |
Current consumption (in no-load operation), typ. | 150 mA |
Inrush current, typ. | 4:00 AM |
I²t | 1 A²·s |
Power loss | |
Power loss, typ. | 4.65 W |
Memory | |
Work memory | |
● integrated | 384 kbyte |
● expandable | No |
Load memory | |
● Plug-in (MMC) | Yes |
● Plug-in (MMC), max. | 8 Mbyte |
● Data management on MMC (after last programming), min. | 10:00 AM |
Backup | |
● present | Yes; Guaranteed by MMC (maintenance-free) |
● without battery | Yes; Program and data |
CPU processing times | |
for bit operations, typ. | 0.05 µs |
for word operations, typ. | 0.09 µs |
for fixed point arithmetic, typ. | 0.12 µs |
for floating point arithmetic, typ. | 0.45 µs |
CPU-blocks | |
Number of blocks (total) | 1 024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used. |
DB | |
● Number, max. | 1 024; Number range: 1 to 16000 |
● Size, max. | 64 kbyte |
FB | |
● Number, max. | 1 024; Number range: 0 to 7999 |
● Size, max. | 64 kbyte |
FC | |
● Number, max. | 1 024; Number range: 0 to 7999 |
● Size, max. | 64 kbyte |
OB | |
● Size, max. | 64 kbyte |
● Number of free cycle OBs | 1; OB 1 |
● Number of time alarm OBs | 1; OB 10 |
● Number of delay alarm OBs | 2; OB 20, 21 |
● Number of cyclic interrupt OBs | 4; OB 32, 33, 34, 35 |
● Number of process alarm OBs | 1; OB 40 |
● Number of DPV1 alarm OBs | 3; OB 55, 56, 57 |
● Number of isochronous mode OBs | 1; OB 61 |
● Number of startup OBs | 1; OB 100 |
● Number of asynchronous error OBs | 6; OB 80, 82, 83, 85, 86, 87 (OB83 only for PROFINET IO) |
● Number of synchronous error OBs | 2; OB 121, 122 |
Nesting depth | |
● per priority class | 16 |
● additional within an error OB | 4 |
Counters, timers and their retentivity | |
S7 counter | |
● Number | 256 |
Retentivity | |
— adjustable | Yes |
— preset | Z 0 to Z 7 |
Counting range | |
— adjustable | Yes |
— counting range / of S7 counters / initial value | 0 |
— counting range / of S7 counters / full-scale value | 999 |
IEC counter | |
● present | Yes |
● Type | SFB |
● Number | Unlimited (limited only by RAM capacity) |
S7 times | |
● Number | 256 |
Retentivity | |
— adjustable | Yes |
— preset | No retentivity |
Time range | |
— time range / of the S7 timers / initial value | 10 ms |
— time range / of the S7 timers / full-scale value | 9 990 s |
IEC timer | |
● present | Yes SFB |
● Type | Unlimited (limited only by RAM capacity) |
● Number | |
Data areas and their retentivity | |
Retentive data area (incl. timers, counters, flags), max. | 128 kbyte |
Flag | |
● Size, max. | 2 048 byte |
● Retentivity available | Yes; MB 0 to MB 2 047 |
● Retentivity preset | MB 0 to MB 15 |
● Number of clock memories | 8; 1 memory byte |
Data blocks | |
● Retentivity adjustable | Yes; via non-retain property on DB |
● Retentivity preset | Yes |
Local data | |
● per priority class, max. | 32 768 byte; Max. 2048 bytes per block |
Address area | |
I/O address area | |
● Inputs | 2 048 byte |
● Outputs | 2 048 byte |
of which distributed | |
— Inputs | 2 048 byte |
— Outputs | 2 048 byte |
Process image | |
● Inputs | 2 048 byte |
● Outputs | 2 048 byte |
● Inputs, adjustable | 2 048 byte |
● Outputs, adjustable | 2 048 byte |
● Inputs, default | 128 byte |
● Outputs, default | 128 byte |
Subprocess images | |
● Number of subprocess images, max. | 1; With PROFINET IO, the length of the user data is limited to 1600 bytes |
Digital channels | |
● Inputs | 16 384 |
— of which central | 1 024 |
● Outputs | 16 384 |
— of which central | 1 024 |
Analog channels | |
● Inputs | 1 024 |
— of which central | 256 |
● Outputs | 1 024 |
— of which central | 256 |
Hardware configuration | |
Number of expansion units, max. | 3 |
Number of DP masters | |
● integrated | 1 |
● via CP | 4 |
Number of operable FMs and CPs (recommended) | |
● FM | 8 |
● CP, PtP | 8 |
● CP, LAN | 10 |
Rack | |
● Racks, max. | 4 |
● Modules per rack, max. | 8 |
Time of day | |
Clock | |
● Hardware clock (real-time) | Yes |
● retentive and synchronizable | Yes |
● Backup time | 6 wk; At 40 °C ambient temperature |
● Deviation per day, max. | 10s, Type.: 2 s |
● Behavior of the clock following POWER-ON | Clock continues running after POWER OFF |
● Behavior of the clock following expiry of backup period | the clock continues at the time of day it had when power was switched off |
Operating hours counter | |
● Number | 1 |
● Number/Number range | 0 |
● Range of values | 0 to 2^31 hours (when using SFC 101) |
● Granularity | 1 h |
● retentive | Yes; Must be restarted at each restart |
Clock synchronization | |
● supported | Yes |
● to MPI, master | Yes |
● to MPI, slave | Yes |
● to DP, master | Yes; With DP slave only slave clock |
● to DP, slave | Yes |
● in AS, master | Yes |
● in AS, slave | Yes |
● on Ethernet via NTP | Yes; As client |
Digital inputs | |
Number of digital inputs | 0 |
Digital outputs | |
Number of digital outputs | 0 |
Analog inputs | |
Number of analog inputs | 0 |
Analog outputs | |
Number of analog outputs | 0 |
Interfaces | |
Number of industrial Ethernet interfaces | 1; 2 ports (switch) RJ45 |
Number of PROFINET interfaces | 1; 2 ports (switch) RJ45 |
Number of RS 485 interfaces | 1; Combined MPI / PROFIBUS DP |
Number of RS 422 interfaces | 0 |
1. Interface | |
Interface type | Integrated RS 485 interface |
Isolated | Yes |
Interface types | |
● RS 485 | Yes |
● Output current of the interface, max. | 200 mA |
Protocols | |
● MPI | Yes |
● PROFIBUS DP master | Yes |
● PROFIBUS DP slave | Yes |
● Point-to-point connection | No |
MPI | |
● Transmission rate, max. | 12 Mbit/s |
Services | |
— PG/OP communication | Yes |
— Routing | Yes |
— Global data communication | Yes |
— S7 basic communication | Yes |
— S7 communication | Yes |
— S7 communication, as client | No; but via CP and loadable FB |
— S7 communication, as server | Yes |
PROFIBUS DP master | |
● Transmission rate, max. | 12 Mbit/s |
● Number of DP slaves, max. | 124 |
Services | |
— PG/OP communication | Yes |
— Routing | Yes |
— Global data communication | No |
— S7 basic communication | Yes |
— S7 communication | Yes |
— S7 communication, as client | No |
— S7 communication, as server | Yes |
— Equidistance | Yes |
— Isochronous mode | Yes; OB 61; isochronous mode can only be used alternatively on PROFIBUS DP or PROFINET IO |
— SYNC/FREEZE | Yes |
— Activation/deactivation of DP slaves | Yes |
— Number of DP slaves that can be simultaneously activated/deactivated, max. | 8 |
— Direct data exchange (slave-to-slave communication) | Yes; as subscriber |
— DPV1 | Yes |
Address area | |
— Inputs, max. | 2 kbyte |
configuration / header | |
Configuration software | |
● STEP 7 | Yes; V5.5 or higher |
configuration / programming / header | |
● Command set | see instruction list 8 |
● Nesting levels | see instruction list |
● System functions (SFC) | see instruction list |
● System function blocks (SFB) | see instruction list |
Programming language | |
— LAD | Yes |
— FBD | Yes |
— STL | Yes |
— SCL | Yes |
— CFC | Yes |
— GRAPH | Yes |
— HiGraph® | Yes |
Know-how protection | |
● User program protection/password protection | Yes |
● Block encryption | Yes; With S7 block Privacy |
Dimensions | |
Width | 40 mm |
Height | 125 mm |
Depth | 130 mm |
Weights | |
Weight, approx. | 340 g |
Be the first to review “Siemens 6ES7 315 2EH14 0AB0 CPU 315 2 PN DP” Cancel reply
Related products
-
Sale!
FX1S-20MR-001 Mitsubishi FX1S PLC Series
16,000.00৳Original price was: 16,000.00৳ .14,000.00৳ Current price is: 14,000.00৳ . Add to cart -
6ED1052 2MD00 0BA8 Siemens Logo Controller
18,000.00৳ Add to cart -
Sale!
Delta PLC DVP32ES200R
21,000.00৳Original price was: 21,000.00৳ .20,500.00৳ Current price is: 20,500.00৳ . Add to cart -
Sale!
Delta DVP28SV11T2 PLC DVP Series
30,000.00৳Original price was: 30,000.00৳ .27,000.00৳ Current price is: 27,000.00৳ . Add to cart
Reviews
There are no reviews yet.