The Mitsubishi MELSEC FX2N 32MR 001 is a digital I/O module designed for use with Mitsubishi FX series PLCs. It has 16 digital input & 16 digital output. This module FX2N 32MR 001 provides a versatile solution for expanding the digital input and output capabilities of the PLC system. Here’s a detailed description of its features, specifications, and typical applications:

Key Features Mitsubishi MELSEC FX2N 32MR 001 

  1. Type: Digital Input/Output Module
  2. I/O Points:
    • Digital Inputs: 16 points
    • Digital Outputs: 16 points
  3. Voltage Rating:
    • Inputs: DC 24V
    • Outputs: DC 24V

Others Product 

Specifications Mitsubishi MELSEC FX2N 32MR 001

  • Digital Inputs:
    • Channels: 16 points
    • Input Voltage: DC 24V
    • Input Current: Approximately 3mA per point
    • Input Type: NPN transistor input
    • Input Impedance: Approximately 2.5kΩ
  • Digital Outputs:
    • Channels: 16 points
    • Output Voltage: DC 24V
    • Output Current: 0.1A per point, maximum 0.5A per module
    • Output Type: NPN transistor output with short-circuit protection
Mitsubishi PLC Module FX2N and the FX2NC PLC’s Specification Remarks
Operation control method Cyclic operation by stored program
I/O control method Batch processing method (when END instruction is executed) I/O refresh instruction is available
Operation processing time Basic instructions: 0.08 msApplied instructions: 1.52 to several 100 ms
Programming language Relay symbolic language + step ladder Step ladder can be used to produce an SFC style program
Program capacity 8000 steps built in Expandable to 16000 steps using additional memory cassette
 Number of instructions Basic sequence instructions: 20 Step ladder instructions: 2 Applied instructions: 125 A Maximum 125 applied instructions are available
I/O configuration Max hardware I/O configuration points 255, dependent on user selection (Max. software addressable Inputs 255, Outputs 255)
Auxiliary relay(M coils) 3072 points M0 to M3071
Auxiliary relay(M coils)
General
Auxiliary relay(M coils) 2572 points (subset) M500 to M3071
Latched
Auxiliary relay(M coils) 256 points From the range M8000 to M8255
Special
State relays (S coils) 1000 points S0 to S999
General
State relays (S coils) Latched 500 points (subset) S500 to S999
State relays (S coils) Initial 10 points (subset) S0 to S9
State relays (S coils) Annunciator 100 points S900 to S999
Timers (T) 100 msec Range: 0 to 3,276.7 sec200 points T0 to T199
Timers (T) 10 msec Range: 0 to 327.67 sec46 points T200 to T245
Timers (T) 1 msec retentive Range: 0 to 32.767 sec4 points T246 to T249
Timers (T) 100 msec retentive Range: 0 to 3,276.7 sec6 points T250 to T255
Counters (C) General 16 bit Range: 1 to 32,767 counts200 points C0 to C199Type: 16 bit up counter
Counters (C) 100 points (subset) C100 to C199Type: 16 bit up counter
General 16 bit
Latched 16 bit
Counters (C) General 16 bit Range: -2,147,483,648 to 2,147,483,64735 points C200 to C234Type: 32 bit up/down counter
General 32 bit
Counters (C) General 16 bit 15 points (subset) C219 to C234Type: 16 bit up/down counter
Latched 32 bit

 

 

Applications:

  • Factory Automation: Ideal for controlling machines, conveyors, and other automated systems that require digital I/O signals.
  • Process Control: Used in applications requiring the control of various digital devices and actuators.
  • Building Automation: Suitable for controlling lighting, HVAC systems, and other building management tasks.

Benefits:

  • Compact Design: Space-saving design suitable for installation in control panels with limited space.
  • Reliability: Robust construction ensures reliable performance in industrial environments.
  • Ease of Installation: Designed for quick and easy installation on a DIN rail, with clear labeling for straightforward wiring.

Installation and Configuration:

  1. Mounting:
    • Secure the FX2N-32MR-001 module on a DIN rail inside a control panel.
  2. Wiring:
    • Connect the digital inputs and outputs to the appropriate terminals, following the wiring diagrams provided in the user manual.
  3. Software Setup:
    • Use Mitsubishi’s GX Works2 or GX Works3 software to configure the module.
      • Define the digital input and output points.
      • Set the input and output parameters, such as input logic type and output control settings.
      • Integrate the module into your PLC program and define the control logic.
  4. Testing:
    • Download the configuration to the PLC.
    • Use the PLC’s diagnostic tools to monitor and verify the operation of the digital inputs and outputs.
    • Conduct thorough testing to ensure all digital signals are correctly processed and controlled.

The FX2N-32MR-001 is a reliable and efficient digital I/O module for Mitsubishi FX series PLCs. It provides 16 digital input and 16 digital output points, making it suitable for a wide range of industrial automation applications. Proper installation and configuration using Mitsubishi’s software tools will ensure that the module operates effectively in your control systems.

 