DVP04DA-E2 Delta Analog Output Module provides 4 (four) flexible analog outputs, high precision (≤0.5% FS), and fast response times, ideal for driving voltage or current inputs in industrial and process control systems of delta Electronics. The Delta DVP-04DA-E2 Module is used to Delta’s DVP‑ES2/EX2 PLC series.  In addition to, we can access the data in the module DVP02DA-E2 or DVP04DA-E2 Analog Output module by applying the instructions TO/FROM or write the output value of channels directly by using MOV instruction.

Specification of 02D/A & DVP04DA-E2 Delta Analog Output Module

Digital/Analog module (02D/A & 04D/A)
Max. rated power consumption 02DA: 1.5W, 04DA: 3W, supply by external power source.
Power Supply Voltage 24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%)
Connector European standard removable terminal block (Pin pitch: 5mm)
 

Protection

Voltage output is protected by short circuit. Short circuit lasting for too long may cause damage on internal circuits. Current output can

be open circuit.

Operation/storage temperature Operation: 0°C~55°C (temperature), 5~95% (humidity), Pollution degree2

Storage: -25°C~70°C (temperature), 5~95% (humidity)

Vibration/shock immunity International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC61131-2 & IEC 68-2-27 (TEST Ea)
Series connection to DVP-PLC MPU The modules are numbered from 0 to 7 automatically by their distance from MPU. Max. 8 modules are allowed to connect to MPU and will not occupy any digital I/O points.
  • Functions Specifications
Digital/Analog module Voltage output Current output
Range of analog output -10V ~ 10V 0 ~ 20mA 4mA ~ 20mA
Range of digital conversion -32,000 ~ +32,000 0 ~ +32,000 0 ~ +32,000
Max./Min. range of digital data -32,768 ~ +32,767 0 ~ +32,767 -6,400 ~ +32,767
Hardware Resolution 14 bits 14 bits 14 bits
Max. output current 5mA
Tolerance load impedance 1KΩ ~ 2MΩ 0 ~ 500Ω
Analog output channel 2 channels or 4 channels / each module
Output impedance 0.5Ω or lower
Overall accuracy ±0.5% when in full scale (25°C, 77°F)

±1% when in full scale within the range of 0 ~ 55°C (32 ~ 131°F)

Response time 400 μ s / each channel
Digital data format 2’s complement of 16 bits
 

 

 

Isolation method

Optical coupler isolation between analog circuits and digital circuits. No isolation among analog channels.

500VDC between digital circuits and Ground 500VDC between analog circuits and Ground 500VDC between analog circuits and digital circuits

500VDC between 24VDC and Ground

 