Delta DVP04PT‑E2 Delta Analog input Module

Delta Analog input Module Delta DVP04PT‑E2 & DVP06PT-E2

Model: DVP04PT-E2/DVP06PT-E2

Brand: Delta

Origin: China

Ask Price Call/WhatsApp: +8801713722455

Description

Delta DVP04PT‑E2 Delta Analog input Module & DVP06PT‑E2 is the Temperature Measurement Module, which part of Delta’s DVPES2 series and DVPEX2 series Programmable Logic Controller (PLC). The Delta DVP04PT‑E2 is a 4 channel analog input module & The Delta DVP06PT‑E2 is a 6 channel analog input module of delta. Both modules are designed for precision temperature monitoring via RTD sensors (Pt100/Pt1000, Ni100/Ni1000) for Delta DVP-ES2 / EX2 PLC systems.

Electrical Specification of Delta DVP04PT‑E2 Delta Analog input Module

Power supply voltage 24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%)
Max. rated power consumption 1.5W, supplied by external power source
Connector European standard removable terminal block (Pin pitch: 5mm)
Operation/storage Operation: 0°C~55°C (temp.), 5~95% (humidity), Pollution degree2 Storage: -25°C~70°C (temp.), 5~95% (humidity)
Vibration/shock immunity International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC61131-2 & IEC 68-2-27 (TEST Ea)
Series connection to DVP-PLC MPU The modules are numbered from 0 to 7 automatically by their distance from MPU. No.0 is the closest to MPU and No.7 is the furthest. Maximum 8 modules are allowed to connect to MPU and will not occupy any digital I/O points.

 

Function Specification of DVP04/06PT-E2

DVP04/06PT-E2 Celsius (°C) Fahrenheit (°F) Input Impedance
Analog input channel 4/6 channels
Digital data format 2’s complement of 16 bits
Response time 200ms / each channel
Overall accuracy ±0.3% when in full scale (25°C, 77°F)
±0.6% when in full scale within the range of 0 ~ 55°C, 32 ~ 131°F
Applicable sensor type 04PT:3-Wire Pt100 (DIN 43760-1980 JIS C1604-1989, 100Ω 3850 PPM/°C);
Pt1000 (DIN EN60751, 1 kΩ 3850 PPM/°C); Ni100 / Ni1000(DIN 43760); 0 ~
300Ω/0 ~ 3000Ω input impedance
06PT:3- Wire Pt100 (DIN 43760-1980 JIS C1604-1989, 100Ω 3850 PPM/°C);
Pt1000 (DIN EN60751, 1 kΩ 3850 PPM/°C) ; Ni100 / Ni1000(DIN 43760);
Cu50;Cu100;JPt100 (JIS C1604-1989);LG-Ni1000;0 ~ 300Ω/0 ~ 3000Ω input
impedance
Input temperature range Pt100: -180°C ~ 800°C Pt100: -180°C ~ 800°C
Ni100: -80°C ~ 170°C Ni100: -80°C ~ 170°C
Pt1000: -180°C ~ 800°C Pt1000: -180°C ~ 800°C
Ni1000: -80°C ~ 170°C Ni1000: -80°C ~ 170°C 0 ~ 300Ω
JPt100: -180°C ~ 500°C JPt100: -180°C ~ 500°C 0 ~ 3000Ω
Cu50: -50°C ~ 150°C Cu50: -50°C ~ 150°C
Cu100: -50°C ~ 150°C Cu100: -50°C ~ 150°C
LG-Ni1000: -50°C ~ 180°C LG-Ni1000: -50°C ~ 180°C
Range of digital conversion Pt100: K-1,800 ~ K8,000 Pt100: K-1,800 ~ K8,000
Ni100: K-800 ~ K1,700 Ni100: K-800 ~ K1,700
Pt1000: K-1,800 ~ K8,000 Pt1000: K-1,800 ~ K8,000
Ni1000: K-800 ~ K1,700 Ni1000: K-800 ~ K1,700 K0 ~ K3,000
JPt100: K-1,800 ~ K5,000 JPt100: K-1,800 ~ K5,000 K0 ~ K30,000
Cu50: K-500 ~ K1,500 Cu50: K-500 ~ K1,500
Cu100: K-500 ~ K1,500 Cu100: K-500 ~ K1,500
LG-Ni1000: K-500 ~ K1,800 LG-Ni1000: K-500 ~ K1,800
Resolution 0.1°C 0.18°F*1 0.1Ω
Average function Range: K1 ~ K100.
Self-diagnosis Upper and lower bound detection in all channels
Isolation Optical coupler isolation between digital circuits and analog circuits. No isolation among analog channels.
500VDC between digital circuits and Ground 500VDC between analog circuits and Ground 500VDC between analog circuits and digital circuits
500VDC between 24VDC and Ground

 