6ES7223 1PH32 0XB0 SM 1223 DC RLY

Description

6ES7223 1PH32 0XB0 SM 1223 DC RLY is a digital input & digital output module of SIMATIC S7-1200 series Programmable Logic Controller (PLC), The Digital I/O SM 1223 module has 8 DI/8 DO, 8 DI 24 V DC, Sink/Source, 8 DO, relay 2 A.

Download Datasheet

Specification of 6ES7223 1PH32 0XB0 SM 1223 DC RLY

 

BrandA3:B33B4A3:B31A3:B28 SIEMENS
Model 6ES7223 1PH32 0XB0
General information
Product type designation SM 1223, DI 8×24 V DC, DQ 8x relay
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
from backplane bus 5 V DC, max. 145 mA
Digital inputs
●    from load voltage L+ (without load), max. 4 mA/input 11 mA/relay
output voltage / header
supply voltage of the transmitters / header
●    present Yes
Power loss
Power loss, typ. 5.5 W
Digital inputs
Number of digital inputs 8
●    in groups of 2
Input characteristic curve in accordance with IEC 61131, type 1 Yes
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max. 8
horizontal installation
— up to 40 °C, max. 8
— up to 50 °C, max. 8
vertical installation
— up to 40 °C, max. 8
Input voltage
●    Type of input voltage DC 24 V
●    Rated value (DC) 5 V DC at 1 mA
●    for signal “0” 15 V DC at 2.5 mA
●    for signal “1”
Input current
●    for signal “0”, max. (permissible quiescent current) 1 mA
●    for signal “1”, min. 2.5 mA 4 mA
●    for signal “1”, typ.
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in
groups of four
for interrupt inputs
— parameterizable Yes
Cable length
●    shielded, max. 500 m
●    unshielded, max. 300 m
Digital outputs
Number of digital outputs 8
●    in groups of 2
Short-circuit protection No; to be provided externally
Switching capacity of the outputs
●    with resistive load, max. 2:00 AM
●    on lamp load, max. 30 W with DC, 200 W with AC
Output voltage
●    Rated value (DC) 5 V DC to 30 V DC
●    Rated value (AC) 5 V AC to 250 V AC
Output current
●    for signal “1” rated value 2:00 AM
●    for signal “1” permissible range, max. 2:00 AM
Output delay with resistive load
●    “0” to “1”, max. 10 ms
●    “1” to “0”, max. 10 ms
Total current of the outputs (per group)
horizontal installation
— up to 50 °C, max. 10 A; Current per mass
Relay outputs
●    Number of relay outputs 8
●    Rated supply voltage of relay coil L+ (DC) 24 V
●    Number of operating cycles, max. mechanically 10 million, at rated load voltage 100 000
Switching capacity of contacts
— with inductive load, max. 2:00 AM
— on lamp load, max. 30 W with DC, 200 W with AC 2 A
— with resistive load, max.
Cable length
●    shielded, max. 500 m
●    unshielded, max. 150 m
Interrupts/diagnostics/status information
Alarms
●    Diagnostic alarm Yes
Diagnostics indication LED
●    for status of the inputs Yes
●    for status of the outputs Yes
Potential separation
Potential separation digital inputs
●    between the channels, in groups of 2
Potential separation digital outputs
●    between the channels Relays 2
●    between the channels, in groups of 1 500 V AC for 1 minute
●    between the channels and backplane bus
Permissible potential difference
between different circuits 750 V AC for 1 minute
Degree and class of protection
IP degree of protection IP20
Standards, approvals, certificates
CE mark Yes
CSA approval Yes
UL approval Yes
cULus Yes
FM approval Yes
RCM (formerly C-TICK) Yes
KC approval Yes
Marine approval Yes
Ambient conditions
Free fall
●   Fall height, max. 0.3 m; five times, in product package
Ambient temperature during operation
●   min. -20 °C
●   max. 60 °C
●   horizontal installation, min. -20 °C
●   horizontal installation, max. 60 °C
●   vertical installation, min. -20 °C
●   vertical installation, max. 50 °C
●   permissible temperature change 5°C to 55°C, 3°C / minute
Ambient temperature during storage/transportation
●   min. -40 °C
●   max. 70 °C
Air pressure acc. to IEC 60068-2-13
●   Storage/transport, min. 660 hPa
●   Storage/transport, max. 1 080 hPa
Relative humidity
●   Operation at 25 ℃ without condensation, max. 95%
connection method
required front connector Yes
Mechanics/material
Enclosure material (front)
●   Plastic Yes
Dimensions
Width 45 mm
Height 100 mm
Depth 75 mm
Weights
Weight, approx. 230 g

 

Others Module

Reviews

There are no reviews yet.

Be the first to review “6ES7223 1PH32 0XB0 SM 1223 DC RLY”

error: Content is protected !!