6ES7288 1ST60 0AA1 S7 200 Smart CPU ST60
Category: Uncategorized
Tags: 6es7 288 1st60 0aa0, 6es7288 1st60 0aa0, 6ES7288 1ST60 0AA1, CPU ST60, S7 200 Smart CPU ST60
Description
6ES7288 1ST60 0AA1 S7 200 Smart CPU ST60 is a Programmable Logic Controller of Siemens SMART Series, The SIMATIC S7-200 SMART, CPU ST60 DC/DC/DC, also has onboard I/O: 36 Digital Input (DI) 24 V DC & 24 Digital Output (DO) 24 V DC; power supply: DC 20.4-28.8V DC, program/data memory 50 KB.
Specification of 6ES7288 1ST60 0AA1 S7 200 Smart CPU ST60
General information | |
Product type designation | CPU ST60 DC/DC/DC |
Engineering with | |
● Programming package | STEP 7 Micro/WIN SMART |
Installation type/mounting | |
Rail mounting | Yes; Standard – DIN rail |
Supply voltage | |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Input current | |
Current consumption, max. | 710 mA; 24 V DC |
Inrush current, max. | 11.5 A; at 28.8 V |
Output current | |
Current output, max. | 300 mA; 24 V DC Sensor Power |
for backplane bus (5 V DC), max. | 1.4 A; max. 5 V DC for EM bus |
Power loss | |
Power loss, max. | 20 W |
Memory | |
Type of memory | DDR |
Flash | Yes Yes |
RAM | 20 kbyte |
Memory available for user data | 30 kbyte; Program memory |
Memory size | Yes; microSDHC Card (optional) |
Micro Memory Card | |
Backup | |
● present | Yes; Maintenance free, RTC requires 7 days. |
CPU processing times | |
for bit operations, typ. | 150 ns; / instruction |
for word operations, typ. | 1.2 µs; / instruction |
for floating point arithmetic, typ. | 3.6 µs; / instruction |
Address area | |
I/O address area | |
● Inputs | 144 byte; 256 bit of digital inputs & 56 words of analog inputs |
● Outputs | 144 byte; 256 bit of digital outputs & 56 words of analog outputs |
Time of day | |
Clock | |
● Type | Hardware clock, no battery backup Yes |
● Hardware clock (real-time) | 7 d |
● Backup time | 120 s; within 120s/month at 25 °C |
● Deviation per day, max. | |
Digital inputs | |
Number of digital inputs | 36; Integrated |
● of which inputs usable for technological functions | 6; HSC (High Speed Counting) Yes |
Source/sink input | |
Number of simultaneously controllable inputs | |
all mounting positions | |
— up to 40 °C, max. | 36 |
Input voltage | |
● Type of input voltage | DC |
● Rated value (DC) | 24 V |
● for signal “0” | I0.0 to I0.3 < 1 V DC; I0.4 to I4.3 < 5 V DC I0.0 to I0.3 > 4V; I0.4 to I4.3 > 15V |
● for signal “1” | |
Input current | |
● for signal “0”, max. (permissible quiescent current) | 1 mA |
● for signal “1”, typ. | 4 mA |
Input delay (for rated value of input voltage) | |
for standard inputs | |
— parameterizable | Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four |
— at “0” to “1”, min. | 0.2 ms |
— at “0” to “1”, max. | 12.8 ms |
for interrupt inputs | |
— parameterizable | Yes |
for technological functions | |
— parameterizable | Yes; 6 Single phase: 4 HSCs at 200 kHz; 2 HSCs at 30 kHz 4 A/B phase: 2 |
HSCs at 100 kHz; 2 HSCs at 20 kHz | |
Cable length | |
● shielded, max. | 500 m; 50m shielded for HSC inputs |
● unshielded, max. | 300 m; for technological functions: No |
Digital outputs | |
Number of digital outputs | 24; Transistor |
● of which high-speed outputs | 3; 100 kHz Pulse Train Output |
Short-circuit protection | No |
Switching capacity of the outputs | |
● with resistive load, max. | 0.5 A |
● on lamp load, max. | 5 W |
Output voltage | |
● for signal “1”, min. | 20 V DC |
Output current | |
● for signal “1” rated value | 0.5 A |
● for signal “0” residual current, max. | 10 µA |
Output delay with resistive load | |
● “0” to “1”, max. | 3 µs; of the standard outputs, max. 3 µs; of the pulse outputs, max. (Q a.0 to Q a.3) 1 µs |
200 µs; of the standard outputs, max. 200 µs; of the pulse outputs, max. (Q a.0 to Q a.3) 50 µs | |
● “1” to “0”, max. | |
Switching frequency | |
● of the pulse outputs, with resistive load, max. | 100 kHz |
Relay outputs | |
● Number of relay outputs | 0 |
Cable length | |
● shielded, max. | 500 m |
● unshielded, max. | 150 m |
Interfaces | |
Number of industrial Ethernet interfaces | 1 |
Number of RS 485 interfaces | 1 |
1. Interface | |
Interface type | PROFINET |
Isolated | Yes; Transformer isolated, 1,500V AC |
automatic detection of transmission rate | Yes; 10/100 Mbit/s |
Autonegotiation | Yes |
Autocrossing | Yes |
Interface types | |
● RJ 45 (Ethernet) | Yes |
Protocols | |
● PROFINET IO Controller | Yes; Since V2.4 |
● PROFINET IO Device | Yes; I-Device since V2.5 |
PROFINET IO Controller | |
● Transmission rate, max. | 100 Mbit/s |
Services | |
— Number of connectable IO Devices, max. | 8 |
— Updating time | 4 ms; The minimum value of the update time also depends on the communication
component set for PROFINET IO, on the number of IO devices and the quantity of configured user data. |
Address area | |
— Inputs, max. | 128 byte; Per device |
— Outputs, max. | 128 byte; Per device |
2. Interface | |
Interface type | RS 485 (max. 187.5 kbps) |
Interface types | |
● RS 485 | Yes |
PROFIBUS DP master | |
Services | |
— S7 communication | Yes |
Protocols | |
Supports protocol for PROFINET IO | Yes; RT Controller (since FW V2.4) & I-Device (since FW V2.5) |
PROFIBUS | Yes; Via CM DP module |
Protocols (Ethernet) | |
● TCP/IP | Yes |
communication functions / header | |
S7 communication | |
● supported | Yes |
● as server | Yes |
● as client | Yes |
Test commissioning functions | |
Forcing | |
● Forcing | Yes |
Integrated Functions | |
PID controller | Yes; PID closed-loop control function: Continuous controller outputs, binary controller outputs, automatic/manual mode, max. 8 loops |
Number of pulse outputs | 3 |
EMC | |
Interference immunity against discharge of static electricity | |
● Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 | Yes |
— Test voltage at air discharge | 8 kV |
— Test voltage at contact discharge | 4 kV |
Interference immunity against high-frequency electromagnetic fields | |
● Interference immunity against high-frequency radiation acc. to IEC 61000-4-3 | Yes; 10 V/m, 80 to 1 000 MHz (to IEC 61000-4-3); 10 V/m, 900 MHz, 1.89 GHz, |
50% ED (to IEC 61000-4-3) | |
Interference immunity to cable-borne interference | |
● Interference immunity on supply lines acc. to IEC 61000- 4-4 | Yes; 2 kV acc. to IEC 61000-4-4, burst |
● Interference immunity on signal cables acc. to IEC 61000- 4-4 | |
Yes; ±2 kV acc. to IEC 61000-4-4, Burst | |
Interference immunity against conducted variable disturbance induced by high-frequency fields | |
● Interference immunity against high frequency current feed acc. to IEC 61000-4-6 | Yes; 10 V, 150 kHz to 80 MHz (to IEC 61000-4-6) |
Emission of radio interference acc. to EN 55 011 | |
● Limit class A, for use in industrial areas | Yes; EN 61000-6-4, interference emission: Intended for use in industrial areas. |
Emission of conducted and non-conducted interference | |
● Interference emission via line/AC current cables | EN 61000-6-4, interference emission: Intended for use in industrial areas. |
Degree and class of protection | |
IP degree of protection | IP20 |
Standards, approvals, certificates | |
CE mark | Yes |
Ambient conditions | |
Free fall | |
● Fall height, max. | 0.3 m; five times, in product package |
Ambient temperature during operation | |
● min. | 0 °C |
● max. | 55 °C |
● horizontal installation, min. | 0 °C |
● horizontal installation, max. | 55 °C |
● vertical installation, min. | 0 °C |
● vertical installation, max. | 45 °C |
Ambient temperature during storage/transportation | |
● min. | -40 °C |
● max. | 70 °C |
Air pressure acc. to IEC 60068-2-13 | |
● Storage/transport, min. | 660 hPa |
● Storage/transport, max. | 1 080 hPa |
Altitude during operation relating to sea level | |
● Installation altitude, min. | -1 000 m |
● Installation altitude, max. | 2 000 m |
Relative humidity | |
● Operation at 25 ℃ without condensation, max. | 95% |
configuration / header | |
configuration / programming / header | |
Programming language | |
— LAD | Yes |
— FBD | Yes |
— STL | Yes |
Dimensions | |
Width | 175 mm |
Height | 100 mm |
Depth | 81 mm |
Weights | |
Weight, approx. | 528.2 g |
Be the first to review “6ES7288 1ST60 0AA1 S7 200 Smart CPU ST60” Cancel reply